Skip to content
Menu

Engineering guide

Cathodic Protection Test Stations: Locations, Types and Wiring

A test station is where the cables from the pipeline, its anodes, coupons and neighbouring structures come to the surface so the cathodic protection can be measured. This guide follows ISO 15589-1:2015 clause by clause: where stations are required, which conductors each type contains, the minimum cable sizes and how cables are attached to the pipe.

ISO 15589-1:2015 Clauses 8.5, 10.7, 11 and Annex A Wiring sketches for 7 station types
Cathodic protection test station terminal board with identified terminals and links
Product visualization; the terminal arrangement follows the project schematic.

Quick answer

What a test station has to let you measure

ISO 15589-1 requires monitoring facilities along the pipeline route so that the performance of the cathodic protection can be measured (ISO 15589-1:2015, 11.1). At commissioning, the following measurements are made at test stations (12.3.4):

  • ON-potential at the extremities of the protected pipeline and at critical locations;
  • ON-potential and current on coupons, if any;
  • potentials of neighbouring foreign structures, to check for any influence on them;
  • ON-potential and current through the bond at bonded structures;
  • ON-potentials that verify the electrical isolation of the pipeline at isolating joints, metal casings, reinforced concrete and earthing systems.

Each of these needs its own conductors, brought to a terminal that can be reached safely. That is why the station type follows its location on the route, and why the terminal schedule matters more than the enclosure style.

Where to install

Spacing and special locations

To monitor pipe-to-electrolyte potentials, currents and possible interference, test stations should be installed along the pipeline at intervals not greater than 3 km in rural areas and 1 km in urban or industrial areas (ISO 15589-1:2015, 11.2).

Required at special features

  • isolating joints; connections to earthing systems; metallic casings;
  • bond connections to other pipelines or facilities;
  • connections with coupons and grounding;
  • impressed current stations and drainage stations. (11.2)

Recommended where the pipeline

  • crosses or runs parallel with a.c./d.c. traction systems, a.c. power lines or other pipelines;
  • crosses major roads and embankments, railways and rivers;
  • crosses highly aggressive soil, can be influenced by shielding, or runs close to other structures with cathodic protection;
  • runs through non-metallic casings, or is used as a shunt for line current measurements. (11.2)

Stations are generally installed above the pipeline and identified. In urban and industrial areas, additional facilities can be needed so the reference electrode has soil contact at the measuring point (11.2 and Note). Line-current test stations are placed at regular distances, approximately every 10 km, and at cathodic protection stations, large river crossings and branch lines (Annex A, A.6).

Station types

Eight station functions and their conductors

ISO 15589-1 describes the contents of a test station by function rather than by catalogue name. A station may hold one or several cables to the pipeline; cables to permanent reference electrodes, coupons, probes, ER probes and d.c. decoupling devices; cables to neighbouring structures; cables to casings; and two or more pipe cables for line current measurements (ISO 15589-1:2015, 11.3). The sketches below show the usual conductor arrangement for each function. They are schematic, not to scale.

Potential test station wiring sketchgradeTest stationP1P2REFCSEPipelinetwo separate pipe connections + optional permanent electrode
Potential station. Two separate conductors on two different connections let the integrity of the connections be checked (11.2). A portable CSE at grade can replace the permanent electrode.
Line current test station wiring sketchgradeLine current stationABCDPipelineABCDmeasured span (B–C)A, D: currentB, C: potential
Line current station. Outer conductors A and D carry the test current; inner conductors B and C measure the voltage drop over the span (Annex A, Figure A.5). Each connection is identified so the current direction can be established (11.8).
Casing test station wiring sketchgradeStation 1Station 2PCSCSPPipelinemetallic casing
Casing station. One conductor on the pipeline and one on the casing; to locate a contact, conductors at both casing ends (11.6).
Isolating joint test station wiring sketchgradeIsolating joint stationSide 1Side 2bond / SPD*PipelineIJ* only where the design requires it
Isolating joint station. A connection on each side of the joint, brought to the same station and sized for a direct, unidirectional or resistive bond and surge protective devices (11.7).
Bond test station at a pipeline crossing, wiring sketchgradeBond stationA1A2B1B2bond: direct, diode or resistorPipeline B(crossing)Pipeline A
Bond station. Two separate conductors on each pipeline at the crossing, ending in a station that can take a direct, unidirectional or resistive bond (11.5).
Coupon test station wiring sketchgradeCoupon stationPCouponREFlinkcouponCSEPipelineremovable link; electrode buried next to the coupon
Coupon station. The coupon is connected to the pipe through an accessible link that can be temporarily disconnected (A.2.5), installed as close to the pipe as possible (11.4).
Galvanic anode test station wiring sketchgradeAnode stationPAnodelinkPipelineanode in backfill3–5 m
Galvanic anode station. The anode cable meets the pipe cable in an accessible station so potential and current can be measured (10.7). Anodes are buried 3 m to 5 m from the pipeline (10.8).
Station functionConductorsISO 15589-1:2015
Pipe-to-soil potentialTwo separate pipe conductors, two connections; optional permanent reference electrode11.2, 11.3
Line currentTwo or more pipe conductors; four for a calibrated span (A, B, C, D)11.3, 11.8, Figure A.5
Cased crossingPipe and casing conductors; at both casing ends to locate a contact11.6
Isolating jointA connection on each side of the joint, to one station11.7
Bond to another pipelineTwo separate conductors on each pipeline11.5
Coupon or probeCoupon or probe cable with a disconnectable link; pipe cable; reference electrode where specified11.4, A.2.5
Galvanic anodeAnode cable and pipe cable joined in an accessible station10.7
Drain pointA test conductor separate from the current drain conductor11.9

At drain points, the separate test conductor is dedicated to the drain-point potential; a test station is not required where the drain point is on an above-ground section of the pipeline (11.9). In a galvanic anode circuit, permanent high-resistance measuring shunts should not be installed, because they reduce the anode current (10.7).

Cables and connections

Minimum cable sizes and how cables are attached

CableMinimum total cross section
Potential measurement2 × 2.5 mm² or 6 mm²
Current span measurement4 × 2.5 mm²
Continuity bond4 × 2.5 mm² or 10 mm²
Galvanic anode system: cable to pipeline4 mm²
Galvanic anode system: cable to a single anode2.5 mm²
Impressed current system: cable to pipeline10 mm²
Impressed current system: cable to groundbed4 × 2.5 mm² or 10 mm²

Source: ISO 15589-1:2015, 8.5.1. The conductor material should be copper. The project design can require larger sections for voltage drop, current, insulation, mechanical strength or temperature.

Separate connections are made between the pipeline and each core or cable with a separate function, so that cables used for potential measurement do not carry current and the reading is not distorted by voltage drop (8.5.1). All conductors in the same station are identified by colour coding or tags (11.2).

Attaching cables to the pipe

  • Connections are made only by competent persons, in accordance with ISO 13847 or documented procedures approved by the pipeline operator. Typical methods include pin brazing, soft soldering, adhesive bonding (measurement cables only), fusion welding with metal deposit, stud welding, a welded steel piece with a pre-welded stud, and aluminothermic welding. (8.5.2)
  • Cable connections are not welded on bends or within 200 mm of pipeline welds, fittings and valves. (8.5.2)
  • For aluminothermic welding, copper penetration into the pipe is less than 1 mm, local hardness stays within the pipe specification, the charge should not exceed 15 g, and it should not be used on corrosion-resistant alloy pipelines. (8.5.2)
  • Connections are checked mechanically (for example a sharp blow with a 1 kg hammer, see EN 12732) and electrically: the resistance of the connection, excluding the cable, should be below 0.1 Ω. The coating is then repaired so that water cannot enter. (8.5.2)

More on cable insulation and installation is in the cathodic protection cable guide.

Enclosure and safety

Enclosure, marking and hazardous areas

  • Test facilities are terminated in a suitable test station or enclosure with easy access to the measuring terminals; all cables are permanently marked or colour coded to identify their purpose, and the facility has a permanent identification label. (ISO 15589-1:2015, 8.5.3)
  • If there is any risk of high a.c. voltage on the pipeline, the measuring facility should be non-metallic (dead face) to avoid electric shock to the operator and the public. (8.5.3)
  • Below-grade or surface boxes need mechanical strength for the expected traffic, for example on highways or inside above-ground installations. (8.5.3)
  • Test facilities should be outside hazardous areas; a station inside a classified area conforms to that classification in accordance with IEC 60079-10-1 or an equivalent standard. (8.5.3)
  • Where the route is remote or regular access is difficult, remote monitoring through cables, telemetry or other data transmission, together with permanent reference electrodes and coupons, should be used. (11.10) See monitoring-ready test stations.

Checklist

What to send for a test station quotation

  1. Station schedule — chainage or location of each station and its function: potential, line current, casing, isolating joint, bond, coupon, anode or drain point.
  2. Terminal schedule or schematic — number of circuits per station: pipe, reference electrode, coupon or probe, anode, casing, foreign line and spare terminals.
  3. Cables — conductor size, insulation, colour code or tag text and length for each circuit, checked against the minimum sections above.
  4. Enclosure — above-ground post, flush or below-grade box with its traffic loading, wall or pedestal box; material; dead-front panel where a.c. voltage is a risk; hazardous-area classification if any.
  5. Internal components — links, shunts and their ratings, bond resistors, diodes or surge protective devices, and any coupons or permanent reference electrodes supplied with the station.
  6. Quantity, labelling and destination — identification labels, packing per station, delivery port and schedule.

Questions

Short answers

How far apart should cathodic protection test stations be?
ISO 15589-1:2015 (11.2) recommends intervals not greater than 3 km in rural areas and 1 km in urban or industrial areas, plus stations at special features such as isolating joints, casings, bonds, impressed current stations and drainage stations, and at crossings with power lines, traction systems, railways, rivers and other pipelines.
Why does a potential test station have two cables to the pipe?
Two separate conductors on two different connections let the integrity of the connections be verified (ISO 15589-1:2015, 11.2). ISO also requires a separate connection for each function, so cables used for potential measurement do not carry current (8.5.1).
What cable size is used for test station leads?
ISO 15589-1:2015 (8.5.1) gives minimum total cross sections of 2 x 2.5 mm2 or 6 mm2 for potential measurement, 4 x 2.5 mm2 for current span measurement, and 4 x 2.5 mm2 or 10 mm2 for a continuity bond. The project design can require larger sizes.
When should a test station be non-metallic?
If there is any risk of high a.c. voltage on the pipeline, ISO 15589-1:2015 (8.5.3) says the measuring facility should be non-metallic (dead face) to avoid electric shock to the operator and members of the public.

Sources

Standards used in this guide

  • ISO 15589-1:2015 Petroleum, petrochemical and natural gas industries — Cathodic protection of pipeline systems — Part 1: On-land pipelines. Clauses 8.5.1, 8.5.2, 8.5.3, 10.7, 10.8, 11.1 to 11.10 and 12.3.4; Annex A: A.2.5, A.6 and Figure A.5.
  • Standards referred to by ISO 15589-1 and named here without quoting their content: ISO 13847, EN 12732, EN 15280 and IEC 60079-10-1.

Values are quoted from the edition listed. Where a project specification, purchase order or CP design states other values, those govern.

Factory supply & quotation

Drawing-Configured CP Test Stations, Coupons & Reference Cells

CathPro builds post-mounted and flush cathodic protection test stations in painted carbon steel, stainless steel, cast aluminum or UV-stabilized enclosures with project-configured brass/stainless terminal boards, shunts, bonding links, polarization coupons, permanent Cu/CuSO4 electrodes and CP cables.

Direct engineering desk (no web form required): sales@cathprocp.com · WhatsApp +86 159 7878 1890